CVIEW-PRC Custom Gas Fireplace
Part No. XG0704
f i r e f e a t u r e
Installation
Note: After gas line is connected, each appliance connection,
valve and valve train must be checked while under normal
operating pressure with either a liquid solution, or leak
detection device, to locate any source of leak. Tighten
any areas where bubbling appears or leak is detected until
bubbling stops completely or leak is no longer detected.
DO NOT use a flame of any kind to test for leaks.
Installing The Gas Line
The gas connection is located on the right side of the lower portion of
the fireplace body. The manufacturer requires a service shut off valve
located in an accessible location to isolate the gas supply. The gas
line must be installed, and tested for leaks before finishing the CVIEW
Fireplace. Natural Gas requires a minimum inlet gas supply pressure
of 5.5" W.C. & a manifold pressure of 3.5" W.C. Propane requires a
minimum inlet gas supply pressure of 11" W.C. & a manifold pressure
of 10" W.C. The manifold outlet pressure is set from the factory to the
appropriate pressure and should be verified. The manufacturer has
provided an inlet pressure tap location in the fireplace for easy access.
The control valves have a provision to remove a 1/8 plug so that a
hose barb fitting can be installed to check pressure.
Figure 6. Gas line access.
Refer to chart on page 3 for correct dimensions.
Figure 5. Combustible surrounds.
LP or NG Hookup
1/2”NPT
Electrical Connection
to Service Panel
Installation Of Electrical Supply
The C-View Fireplace is supplied with an external electrical Control
Panel pre-wired by the factory. The standard gas control cable is 15
feet between the fireplace and the external panel, additional length
is available upon request. The external panel is 16" x 16" x 6" and
must be located in an accessible location. The C-View requires 120V
electrical supply on a dedicated 15 amp fuse or circuit breaker to
the Control Panel
6”
MIN
Page 7
Installing The Remote Switch
The CVIEW-PRC's two gas valves, located inside the unit and under-
neath the burner, may be connected to a wall switch or a hand-held
remote. The valve operates on a 24V circuit. DO NOT connect the
gas valve to an external circuit. The external electrical panel supplied
with the fireplace is equipped with a 20 foot low voltage wire, for con-
necting to a wall switch of your choice, longer lengths are an option.
The electrical panel has three connection boxes on the side of the
panel marked: 110 Volt Power Supply, Power Vent Motor, and Gas
Control Wiring.
First Connect the White, Black, and Green (Ground) wire coming
from the power vent motor in the box marked Power Vent Motor. Then
connect the cable from the fireplace. Last connect the power supply to
the box marked 110 Volt Power Supply. See the diagram on page 9
for the cable installation.
Figure 7. Electrical Supply
CAUTION:
Do not obstruct, or attempt to conceal, the vent termination.
These actions will affect the operation of the fireplace, and may
be hazardous.
In heavy snow areas, take extra care to prevent snow buildup
from obstructing the vent termination.
Installations in Canada must be electrically grounded in accordance
with CSA C22.1 Canadian Electrical Code Part 1 and/or Local Codes.
Installations in the USA must be electrically grounded in accordance
with local codes or, in the absence of local codes, with the National
Electrical Code, ANSI/NFPA 70-1987.
1
10V Power Supply
Power Vent Motor
Gas Control Wiring
Wall Switch
Air Proving Switch
Fuse
Fan Speed
Control
Post Purge
Control